Health & Saf. Code, § 13114 · Article 1. General
Health & Saf. Code, § 13114
Text — As published in the Legislative Counsel's database, tables dated October 18, 2026 (pubinfo_2025.zip)
(a) The State Fire Marshal, with the advice of the State Board of Fire Services, shall adopt regulations and standards as he or she may determine to be necessary to control the quality and installation of fire alarm systems and fire alarm devices marketed, distributed, offered for sale, or sold in this state.
(b) (1) No person shall market, distribute, offer for sale, or sell any fire alarm system or fire alarm device in this state unless the system or device has been approved and listed by the State Fire Marshal.
(2) (A) Except as provided in subparagraph (B), commencing July 1, 2014, in order to be approved and listed by the State Fire Marshal, a smoke alarm that is only operated by a battery shall contain a nonreplaceable, nonremovable battery that is capable of powering the smoke alarm for at least 10 years.
(B) This paragraph shall not apply to smoke alarms that have been ordered by, or are in the inventory of, an owner, managing agent, contractor, wholesaler, or retailer on or before July 1, 2014, until July 1, 2015.
(3) Commencing January 1, 2015, in order to be approved and listed by the State Fire Marshal, a smoke alarm shall display the date of manufacture on the device, provide a place on the device where the date of installation can be written, and incorporate a hush feature.
(4) The State Fire Marshal shall have the authority to create exceptions to paragraphs (2) and (3) through its regulatory process. The exceptions that may be considered as part of the regulatory process shall include, but are not limited to, fire alarm systems with smoke detectors, fire alarm devices that connect to a panel, or other devices that use a low-power radio frequency wireless communication signal.
(5) The State Fire Marshal shall approve the manufacturer’s instructions for each smoke alarm and shall ensure that the instructions are consistent with current building standard requirements for the location and placement of smoke alarms.
Notes and commentary — not statutory text
History
Amended by Stats. 2013, Ch. 183, Sec. 21. (SB 745) Effective January 1, 2014.
Source of truth
- Edition
- As published in the Legislative Counsel's database, tables dated October 18, 2026 (pubinfo_2025.zip)
- Official file
- https://leginfo.legislature.ca.gov/faces/codes_displaySection.xhtml?lawCode=HSC§ionNum=13114.
- Text hash
- sha256 422c950ae146f1a899c2129683844f3a484a4f81349d215a0474a4c61d3a68e8
- Composed by
- compose_ca.py 2026-10-22: the Legislative Counsel's CAML content files read by a tokenizer (caml_readers.reader_a); an independent xml.etree reading (caml_readers.reader_b) agrees on every section
Cited by 4 provisions
Provisions in this library whose text cites Health & Saf. Code, § 13114. Each shows the citation as that text prints it.
Procedural information only. Not legal advice and not a substitute for the advice of an attorney. Confirm the current text with the official publisher before relying on it.